日韩中文字,真实的强奸乱伦AⅤ大全网站,中文字幕亚洲色图一区二区,后宫时间THEANIMATIONFeast2,插插射射深夜国产,日本高清播放器在线观看

歡迎來到思途醫(yī)療科技有限公司官網!

醫(yī)療器械生產企業(yè)合規(guī)技術咨詢服務

注冊備案 · 臨床試驗 · 體系建立輔導 · 分類界定 · 申請創(chuàng)新

186-0382-3910
186-0382-3910
全部服務分類
當前位置: 首頁 > 資訊中心 > 知識分享

GMP潔凈室HVAC系統(tǒng),是否可以在夜間關閉?

發(fā)布日期:2024-11-19 閱讀量:次

Can the ventilation of GMP clean rooms be switched off overnight?
GMP潔凈室的通風系統(tǒng)是否可以在夜間關閉?

The ventilation systems of clean rooms consume a lot of energy, especially power for the ventilating fan, refrigerating capacity for cooling and dehumidification in summer as well as heating for warming and steam for humidification in winter. Therefore, the question comes up again and again whether one might switch off the ventilation of the rooms overnight or when they are not used in order to save energy.

GMP潔凈室HVAC系統(tǒng),是否可以在夜間關閉?(圖1)

潔凈室的通風系統(tǒng)耗費巨大能源,特別是通風系統(tǒng)的風扇、夏天致冷和除濕以及冬天加熱和加濕用蒸汽。因此,一直就有這個問題:公司是否可以在晚上或不用的時候關閉房間的通風,以節(jié)約能源?

It is not advised to switch off the ventilation system completely, it is rather advised not to do it. Premises, pressure conditions, microbiology, everything would be out of control during that time. This would make the subsequent measures for the restoration of the GMP-compliant state very complex because each time a requalification would be necessary to reach the normal GMP-compliant state.

一般不建議完全關閉通風系統(tǒng),事實上最好不要這樣做。設施、壓差條件、微生物,在此期間所有東西都有可能失控。這會讓之后的恢復GMP符合狀態(tài)所需的措施非常復雜,因為每次都要做再確認,來達到正常的GMP符合狀態(tài)。

But a reduction in the performance of the ventilation systems (reduction of the air volume by reducing the performance of the ventilation system) is possible, and is already carried out in some companies. Here too, however, the GMP-compliant state must be achieved prior to using the clean room again and this procedure must be validated.

但是,可以降低通風系統(tǒng)的頻率(通過減少通風系統(tǒng)的頻率來減少換氣量),已經有一些公司在這么做了。但是,在重新使用潔凈室之前還是必須達到GMP符合狀態(tài),并且該程序必須經過驗證

For this purpose the following points must be observed:

為此必須要觀察以下幾點:

The reduction can only be carried out so far that the clean room specific limits prescribed for the relevant case are not violated in general. These limits have to be defined in each case for the operating status and the reduction mode including permissible minimum and maximum values, such as clean room class (particle count with equivalent particle size), product specific values (temperature, relative humidity), pressure conditions (pressure difference between the rooms). Note that the values in reduction mode have to be chosen in such a way that the facility has reached the GMP-compliant state in due time before production begins (integration of a time program). This state depends on different parameters such as building material and performance of the system etc. The pressure conditions should be maintained all the time, this means that a reversion of the flow direction is not allowed.

降低通風系統(tǒng)的頻率只能達到一個指定的程度,以確保維持特定個例中的潔凈室的特定限度。在每個個例中,這些運行狀態(tài)下的和降低頻率狀態(tài)下的限度必須定義,其中包括允許的最小和最大值,例如潔凈室級別(粒子數和相關的粒徑)、產品特定的值(溫度、相對濕度)、壓差條件(房間之間的壓差)。注意,在降低頻率的模式下的值的選擇必須使得設施在生產開始之前的規(guī)定時間內(時間計劃結合在其中)達到GMP符合狀態(tài)。此狀態(tài)取決于不同的參數,例如建筑材料和系統(tǒng)性能等。應在所有的時間內都維持壓差條件,這表示不允許氣流逆向。

Furthermore, the installation of an independent clean room monitoring system is recommended in any case in order to constantly monitor and document the above mentioned clean room specific parameters. Thus, the conditions of the area concerned can be monitored and documented at any time. In the case of deviations (reaching of a limit) and in the individual case it is possible to access the measurement and control technology of the ventilation system and to carry out the relevant adjustments.

還有,建議安裝一個獨立的潔凈室監(jiān)測系統(tǒng),這樣可以連續(xù)監(jiān)測并記錄上述潔凈室指定參數。這樣,所關注的區(qū)域的條件應可以在任何時間進行監(jiān)測和記錄。如果有偏差發(fā)生(達到限度),在個案中有可能具備測量和通風系統(tǒng)控制技術,進行相關調整。

During the reduction attention should be paid to ensuring that no unpredicted external interfering influences such as the entry of persons are allowed. For this the installation of a corresponding entry control is advised. In the case of an electronic locking system the entry authorisation can be linked with the above mentioned time program as well as with the independent clean room monitoring system so that entry is authorised only subject to compliance with the predefined requirements.

在降低風機頻率時,要注意確保沒有非預期的外來干擾影響,例如,人員進入。這種情況建議使用相應的人員進出控制。如果使用的是電子鎖系統(tǒng),進出權限可以與上述時間計劃相關聯(lián),以及與獨立的潔凈室監(jiān)測系統(tǒng)相關聯(lián),這樣,進出授權必須要符合預定的要求。

In principal, both states must be qualified first and then requalified in regular intervals and the customary measurements for the regular operating status such as the recovery time measurement in case of a complete failure of the facility must be carried out. In the case a clean room monitoring system exists it is in principal not required - as mentioned above - to carry out further measurements at the start of operations after reduction mode if the procedure is validated. Special focus should be put on the procedure of restarting since temporary reversions of the flow direction are possible, for instance.

原則上來說,兩種狀態(tài)都必須先確認,然后進行定期再確認。通常,常規(guī)運行狀態(tài)下的測量,例如設備完全失效情形下恢復時間測量是必須要進行的。如果存在有潔凈室監(jiān)測系統(tǒng),程序經過驗證的話,原則上不需要---如上所述---在降低通風頻率后重新開始運行時進行進一步測量。特別要注意的是重新開始運行時的程序,因為,比如氣流方向短時逆向是有可能發(fā)生的。

All in all about 30 % of the energy costs can be saved depending on the mode of operation and the shift model but additional investment costs might have to be offset.

總體來說,根據運行模式和當班模式的不同,大概能節(jié)約30%左右的能源,但可能會被額外的投資成本所抵消。

WHO非無菌空調GMP指南

GOOD MANUFACTURING PRACTICES FOR HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS FOR NON-STERILE PHARMACEUTICAL DOSAGE FORMS: PART 2 INTERPRETATION OF PART 1 – GMP FOR HVAC SYSTEMS

非無菌制劑暖通空調GMP指南:第二部分——HVAC系統(tǒng)的GMP要求

It is recommended that the HVAC system be operational on an ongoing basis. Where a manufacturer decides to use energy saving modes or switch some selected AHUs off at specified intervals such as overnight, weekends or extended periods of time, care should be taken to ensure that materials and products are not affected. In such cases, the decision, procedures and records should be sufficiently documented and should include risk assessment, standard operating procedures (SOPs), records and validation. This includes procedures and records for the start-up and shut-down sequence of air handling units.

建議HVAC系統(tǒng)持續(xù)運行。當決定在特定時間使用節(jié)能模式或選擇關閉部分AHU,如夜間、周末或很長時間,應關注確保物料和產品不受影響。這種情況下,應充分記錄該決定、規(guī)程和記錄,并包括風險評估、標準操作規(guī)程(SOP)、記錄驗證。這包括風機處理單元(AHU)的開啟和關閉順序的規(guī)程和記錄

GB 50457-2019
醫(yī)藥工業(yè)潔凈廠房設計標準

9.2.15 無菌藥品生產的潔凈區(qū)凈化空氣調節(jié)系統(tǒng)應保持連續(xù)運行,維持相應的潔凈級別。在非生產期間,凈化空氣調節(jié)系統(tǒng)可以采用低頻運行等模式,但仍應保持醫(yī)藥潔凈室相應級別和對周圍低級別潔凈區(qū)的正壓。因故停機再次開啟空氣凈化系統(tǒng),應當進行必要的測試以確認滿足其規(guī)定的潔凈度級別要求。

GB 50457-2019
醫(yī)藥工業(yè)潔凈廠房設計標準
條文說明

“在非生產時間,由于潔凈室內主要污染源(操作人員)的撤離,室內的發(fā)塵量大大降低,為了節(jié)省運行費用,在滿足潔凈級別和正壓的前提條件下,可以采用降低空氣凈化系統(tǒng)風量方法。”

“對于無菌生產核心區(qū)建議維持正常生產運行時的關鍵參數,對于其他醫(yī)藥潔凈室需維持的正壓值應根據產品特性、生產運行時的情況,QA部門質量驗證的結果及企業(yè)自身生產管理水平而定?!?/p>

新版GMP指南(2023版)

廠房設施和設備分冊

3.6.2.4 節(jié)能模式下的風量平衡

非生產模式作為凈化空調系統(tǒng)的一個運行模式,應保持連續(xù)運行,維持相應的凈化級別和對周圍區(qū)域的正壓,維持良好的氣流方向。凈化空調系統(tǒng)的送風量變化、不同潔凈區(qū)域的風量變化、潔凈室風量的變化,都需要凈化空調系統(tǒng)來實現(xiàn)機組風量、區(qū)域風量及潔凈室風量的再平衡。

1、無菌區(qū)風量可維持規(guī)范范圍內的下限運行。

2、其他潔凈區(qū)可以較大幅度降低運行風量。

說明:由于凈化空調系統(tǒng)送風管道內壓力的差異,不同區(qū)域風量變化存在差異,當系統(tǒng)總風量降低時,不同區(qū)域風量的降低存在區(qū)別,凈化空調系統(tǒng)的風量平衡就會被破壞,從而造成潔凈室的壓力梯度紊亂。同時,為維持區(qū)域正壓,凈化空調系統(tǒng)的新風量應依據正壓需要進行調整。

凈化空調系統(tǒng)生產模式動態(tài)工藝運行、非生產模式運行都需要再平衡系統(tǒng)風量區(qū)域的風量。

實施方式:

1、首先完成非生產模式下凈化空調系統(tǒng)的系統(tǒng)送風量、潔凈區(qū)域送風量的測算設置好非生產模式下的需求風量;

2、凈化空調系統(tǒng)采用設置好的非生產模式風量運行,進行相關的環(huán)境參數測試并通過測試的參數對風量進行調整;

3、通過測試確認在滿足環(huán)境凈化級別及正壓需求下的各風量,確認非生產模式下凈化空調系統(tǒng)的運行設定參數;

采用非生產模式運行,再次確認潔凈環(huán)境的凈化級別和參數,并確認生產模式與非生產模式的自動切換過程。

經過確認后的非生產模式可以作為凈化空調系統(tǒng)的一個運行模式,在生產結束后,自動切入非生產模式運行。

思途企業(yè)咨詢

站點聲明

本網站所提供的信息僅供參考之用,并不代表本網贊同其觀點,也不代表本網對其真實性負責。圖片版權歸原作者所有,如有侵權請聯(lián)系我們,我們立刻刪除。如有關于作品內容、版權或其它問題請于作品發(fā)表后的30日內與本站聯(lián)系,本網將迅速給您回應并做相關處理。
鄭州思途醫(yī)療科技有限公司專注于醫(yī)療器械產品政策與法規(guī)規(guī)事務服務,提供產品注冊備案申報代理、臨床試驗、體系建立輔導、分類界定、申請創(chuàng)新辦理服務。

八年

醫(yī)療器械服務經驗

多一份參考,總有益處

聯(lián)系思途,免費獲得專屬《落地解決方案》及報價

咨詢相關問題或咨詢報價,可以直接與我們聯(lián)系

思途CRO——醫(yī)療器械注冊臨床第三方平臺

在線咨詢
186-0382-3910免費獲取醫(yī)療器械注冊落地解決方案
在線客服
服務熱線

北京公司
186-0382-3911

鄭州公司
186-0382-3910

合肥公司
188-5696-0331

微信咨詢
返回頂部
丹凤县| 江油市| 茶陵县| 建湖县| 吉木萨尔县| 霍城县| 仙居县| 从化市| 凤翔县| 新乡县| 光山县| 巴林左旗| 金秀| 德格县| 临江市| 彭阳县| 永顺县| 湘乡市|